[DIY] Re: tile backsplash and electrical outlets
26 June 2013
Re: [DIY] Re: Cork Floors
I went to Ho-De and got a little free sample of the cork floor tiles. I scratched it with my finger nail and it did scratch but I think it would kind of mend over with just a touch up of some color. Thanks you for the site. I will have to check it out.Joan O.
Reply via web post | Reply to sender | Reply to group | Start a New Topic | Messages in this topic (5) |
25 June 2013
[DIY] Re: Cork Floors
Reply via web post | Reply to sender | Reply to group | Start a New Topic | Messages in this topic (4) |
Re: [DIY] Electric Question
On Jun 25, 2013, at 10:47 AM, Ron Johnson <l0c0l0b0@hotmail.com> wrote:
Can you go AROUND the cement? It might be a longer run, but the cost may be a little less and you won't be ripping it apart. Hopefully the garage door opener is on the garage lights circuit. If they are all connected as you say, check the load and see if it can be done. Otherwise you may need to divide the circuit into two different circuits, depending on the availability in the box.
To: DoIt_Yourself@yahoogroups.com
From: frankruggiero@me.com
Date: Tue, 25 Jun 2013 14:43:10 +0000
Subject: Re: [DIY] Electric QuestionI am sorry if I confused you. There are no wires at all yet. The electrician is going to run new PVC tubing to the areas where the lights will be.I guess my real issue is that I rather tap into the junction box that is there, instead of ripping my basement apart to run a new line. But as DCWired said, I probably need to see what else is running off that line. I have a feeling my garage door is on that line, and maybe some of my kitchen. So I am fearful that it will get overloaded.Ill have to test in and see what is really connected to that line.Im waiting for the electrician to call me back. I am just trying to understand it more, so that I dont get taken advantage of.
On Jun 25, 2013, at 10:37 AM, Ron Johnson <l0c0l0b0@hotmail.com> wrote:How old is that wire? I've come across underground conduit that has been a problem for the wires underneath because of trees or a break in the line got water in the conduit. Don't let him run a new line unless it's necessary. If he insists, check with another electrician.
You can rerun wires through the conduit if you wish. But first, check the continuity of the wires by disconnecting at both ends and check to see if any two are shorted or any is shorted with the conduit. If not, twist together one end and check for opens on the other. That should tell you if there is a problem with the wires that were run. If there are no opens or shorts, you probably don't want to run new wire. If there is a problem connect the new wiring to the old and pull through.
To: DoIt_Yourself@yahoogroups.com
From: frankruggiero@me.com
Date: Tue, 25 Jun 2013 07:46:35 -0400
Subject: Re: [DIY] Electric Question
Yes, underground. But this is all starting from a clean slate. A patio will be built over the electric wires.I'm just having a hard time figuring out an easy way to get the electric outside, without making a complete mess of my basement.Electrician wants to run a new line, but I am wondering if I can just tap into the junction box that is there. I am not sure if he saw that box.But I get the fact that it depends onWhat else is being powered. I will have to look into that.
Sent from my iPhoneI would also be concerned as to how you're running the wire. Underground, is what I'm thinking. Is it an existing column where there are wires run already?
To: DoIt_Yourself@yahoogroups.com
From: dcwired@att.net
Date: Mon, 24 Jun 2013 22:08:37 -0500
Subject: Re: [DIY] Electric Question
It depends on the current load of the circuit and what size of new lights you plan to use. Find the breaker controlling the existing light and see what else it turns off. Find this out and let us know.
On 6/24/2013 9:53 PM, Frank Ruggiero wrote:Hi Electricians.
I am hoping to build 3 light columns in my backyard. I noticed I have a junction box mounted to my foundation which powers a light above my back door.
Is it possible to tap into that box to power the 3 additional light columns.
Does anyone see an issue with powering 4 lights from one standard box?
Excuse my ignorance on electric. I want to do this in the least invasive way and I am hoping that I can use this box to extend my lighting.
By the way, the light switch in my kitchen controls the box, which would be ideal in this setup.
Any thoughts?
Frank
Sent from my iPhone
Re: [DIY] Electric Question
On Jun 25, 2013, at 10:52 AM, Ray Kornele <krazykyngekorny@gmail.com> wrote:
DO NOT run the wire under the slab. Wait until the slab is poured, and run it along one edge of the slab. You can put it, say, four inches under the slab. If it is under the slab and getgs damaged, you have to ruin the slab to get to it.
KrazyKyngeKorny (Krazy, not stupid)
To: DoIt_Yourself@yahoogroups.com
From: frankruggiero@me.com
Date: Tue, 25 Jun 2013 07:46:35 -0400
Subject: Re: [DIY] Electric Question
Yes, underground. But this is all starting from a clean slate. A patio will be built over the electric wires.
Re: [DIY] Electric Question
KrazyKyngeKorny (Krazy, not stupid)
To: DoIt_Yourself@yahoogroups.com
From: frankruggiero@me.com
Date: Tue, 25 Jun 2013 07:46:35 -0400
Subject: Re: [DIY] Electric Question
Yes, underground. But this is all starting from a clean slate. A patio will be built over the electric wires.
Reply via web post | Reply to sender | Reply to group | Start a New Topic | Messages in this topic (9) |
RE: [DIY] Electric Question
To: DoIt_Yourself@yahoogroups.com
From: frankruggiero@me.com
Date: Tue, 25 Jun 2013 14:43:10 +0000
Subject: Re: [DIY] Electric Question
On Jun 25, 2013, at 10:37 AM, Ron Johnson <l0c0l0b0@hotmail.com> wrote:
How old is that wire? I've come across underground conduit that has been a problem for the wires underneath because of trees or a break in the line got water in the conduit. Don't let him run a new line unless it's necessary. If he insists, check with another electrician.
You can rerun wires through the conduit if you wish. But first, check the continuity of the wires by disconnecting at both ends and check to see if any two are shorted or any is shorted with the conduit. If not, twist together one end and check for opens on the other. That should tell you if there is a problem with the wires that were run. If there are no opens or shorts, you probably don't want to run new wire. If there is a problem connect the new wiring to the old and pull through.
To: DoIt_Yourself@yahoogroups.com
From: frankruggiero@me.com
Date: Tue, 25 Jun 2013 07:46:35 -0400
Subject: Re: [DIY] Electric Question
Yes, underground. But this is all starting from a clean slate. A patio will be built over the electric wires.I'm just having a hard time figuring out an easy way to get the electric outside, without making a complete mess of my basement.Electrician wants to run a new line, but I am wondering if I can just tap into the junction box that is there. I am not sure if he saw that box.But I get the fact that it depends onWhat else is being powered. I will have to look into that.
Sent from my iPhoneI would also be concerned as to how you're running the wire. Underground, is what I'm thinking. Is it an existing column where there are wires run already?
To: DoIt_Yourself@yahoogroups.com
From: dcwired@att.net
Date: Mon, 24 Jun 2013 22:08:37 -0500
Subject: Re: [DIY] Electric Question
It depends on the current load of the circuit and what size of new lights you plan to use. Find the breaker controlling the existing light and see what else it turns off. Find this out and let us know.
On 6/24/2013 9:53 PM, Frank Ruggiero wrote:Hi Electricians.
I am hoping to build 3 light columns in my backyard. I noticed I have a junction box mounted to my foundation which powers a light above my back door.
Is it possible to tap into that box to power the 3 additional light columns.
Does anyone see an issue with powering 4 lights from one standard box?
Excuse my ignorance on electric. I want to do this in the least invasive way and I am hoping that I can use this box to extend my lighting.
By the way, the light switch in my kitchen controls the box, which would be ideal in this setup.
Any thoughts?
Frank
Sent from my iPhone
Reply via web post | Reply to sender | Reply to group | Start a New Topic | Messages in this topic (8) |
Re: [DIY] Electric Question
On Jun 25, 2013, at 10:37 AM, Ron Johnson <l0c0l0b0@hotmail.com> wrote:
How old is that wire? I've come across underground conduit that has been a problem for the wires underneath because of trees or a break in the line got water in the conduit. Don't let him run a new line unless it's necessary. If he insists, check with another electrician.
You can rerun wires through the conduit if you wish. But first, check the continuity of the wires by disconnecting at both ends and check to see if any two are shorted or any is shorted with the conduit. If not, twist together one end and check for opens on the other. That should tell you if there is a problem with the wires that were run. If there are no opens or shorts, you probably don't want to run new wire. If there is a problem connect the new wiring to the old and pull through.
To: DoIt_Yourself@yahoogroups.com
From: frankruggiero@me.com
Date: Tue, 25 Jun 2013 07:46:35 -0400
Subject: Re: [DIY] Electric Question
Yes, underground. But this is all starting from a clean slate. A patio will be built over the electric wires.I'm just having a hard time figuring out an easy way to get the electric outside, without making a complete mess of my basement.Electrician wants to run a new line, but I am wondering if I can just tap into the junction box that is there. I am not sure if he saw that box.But I get the fact that it depends onWhat else is being powered. I will have to look into that.
Sent from my iPhone
I would also be concerned as to how you're running the wire. Underground, is what I'm thinking. Is it an existing column where there are wires run already?
To: DoIt_Yourself@yahoogroups.com
From: dcwired@att.net
Date: Mon, 24 Jun 2013 22:08:37 -0500
Subject: Re: [DIY] Electric Question
It depends on the current load of the circuit and what size of new lights you plan to use. Find the breaker controlling the existing light and see what else it turns off. Find this out and let us know.
On 6/24/2013 9:53 PM, Frank Ruggiero wrote:Hi Electricians.
I am hoping to build 3 light columns in my backyard. I noticed I have a junction box mounted to my foundation which powers a light above my back door.
Is it possible to tap into that box to power the 3 additional light columns.
Does anyone see an issue with powering 4 lights from one standard box?
Excuse my ignorance on electric. I want to do this in the least invasive way and I am hoping that I can use this box to extend my lighting.
By the way, the light switch in my kitchen controls the box, which would be ideal in this setup.
Any thoughts?
Frank
Sent from my iPhone
RE: [DIY] Electric Question
You can rerun wires through the conduit if you wish. But first, check the continuity of the wires by disconnecting at both ends and check to see if any two are shorted or any is shorted with the conduit. If not, twist together one end and check for opens on the other. That should tell you if there is a problem with the wires that were run. If there are no opens or shorts, you probably don't want to run new wire. If there is a problem connect the new wiring to the old and pull through.
To: DoIt_Yourself@yahoogroups.com
From: frankruggiero@me.com
Date: Tue, 25 Jun 2013 07:46:35 -0400
Subject: Re: [DIY] Electric Question
Sent from my iPhone
I would also be concerned as to how you're running the wire. Underground, is what I'm thinking. Is it an existing column where there are wires run already?
To: DoIt_Yourself@yahoogroups.com
From: dcwired@att.net
Date: Mon, 24 Jun 2013 22:08:37 -0500
Subject: Re: [DIY] Electric Question
It depends on the current load of the circuit and what size of new lights you plan to use. Find the breaker controlling the existing light and see what else it turns off. Find this out and let us know.
On 6/24/2013 9:53 PM, Frank Ruggiero wrote:Hi Electricians.
I am hoping to build 3 light columns in my backyard. I noticed I have a junction box mounted to my foundation which powers a light above my back door.
Is it possible to tap into that box to power the 3 additional light columns.
Does anyone see an issue with powering 4 lights from one standard box?
Excuse my ignorance on electric. I want to do this in the least invasive way and I am hoping that I can use this box to extend my lighting.
By the way, the light switch in my kitchen controls the box, which would be ideal in this setup.
Any thoughts?
Frank
Sent from my iPhone
Reply via web post | Reply to sender | Reply to group | Start a New Topic | Messages in this topic (6) |
RE: [DIY] Electric Question
From: DoIt_Yourself@yahoogroups.com [mailto:DoIt_Yourself@yahoogroups.com] On Behalf Of Frank Ruggiero
Sent: Tuesday, June 25, 2013 06:47
To: DoIt_Yourself@yahoogroups.com
Subject: Re: [DIY] Electric Question
Sent from my iPhone
I would also be concerned as to how you're running the wire. Underground, is what I'm thinking. Is it an existing column where there are wires run already?
To: DoIt_Yourself@yahoogroups.com
From: dcwired@att.net
Date: Mon, 24 Jun 2013 22:08:37 -0500
Subject: Re: [DIY] Electric Question
It depends on the current load of the circuit and what size of new lights you plan to use. Find the breaker controlling the existing light and see what else it turns off. Find this out and let us know.
On 6/24/2013 9:53 PM, Frank Ruggiero wrote:Hi Electricians.
I am hoping to build 3 light columns in my backyard. I noticed I have a junction box mounted to my foundation which powers a light above my back door.
Is it possible to tap into that box to power the 3 additional light columns.
Does anyone see an issue with powering 4 lights from one standard box?
Excuse my ignorance on electric. I want to do this in the least invasive way and I am hoping that I can use this box to extend my lighting.
By the way, the light switch in my kitchen controls the box, which would be ideal in this setup.
Any thoughts?
Frank
Sent from my iPhone
Reply via web post | Reply to sender | Reply to group | Start a New Topic | Messages in this topic (5) |
Re: [DIY] Electric Question
Sent from my iPhone
I would also be concerned as to how you're running the wire. Underground, is what I'm thinking. Is it an existing column where there are wires run already?
To: DoIt_Yourself@yahoogroups.com
From: dcwired@att.net
Date: Mon, 24 Jun 2013 22:08:37 -0500
Subject: Re: [DIY] Electric Question
It depends on the current load of the circuit and what size of new lights you plan to use. Find the breaker controlling the existing light and see what else it turns off. Find this out and let us know.
On 6/24/2013 9:53 PM, Frank Ruggiero wrote:Hi Electricians.
I am hoping to build 3 light columns in my backyard. I noticed I have a junction box mounted to my foundation which powers a light above my back door.
Is it possible to tap into that box to power the 3 additional light columns.
Does anyone see an issue with powering 4 lights from one standard box?
Excuse my ignorance on electric. I want to do this in the least invasive way and I am hoping that I can use this box to extend my lighting.
By the way, the light switch in my kitchen controls the box, which would be ideal in this setup.
Any thoughts?
Frank
Sent from my iPhone
Reply via web post | Reply to sender | Reply to group | Start a New Topic | Messages in this topic (4) |
RE: [DIY] Electric Question
To: DoIt_Yourself@yahoogroups.com
From: dcwired@att.net
Date: Mon, 24 Jun 2013 22:08:37 -0500
Subject: Re: [DIY] Electric Question
On 6/24/2013 9:53 PM, Frank Ruggiero wrote:
Hi Electricians.
I am hoping to build 3 light columns in my backyard. I noticed I have a junction box mounted to my foundation which powers a light above my back door.
Is it possible to tap into that box to power the 3 additional light columns.
Does anyone see an issue with powering 4 lights from one standard box?
Excuse my ignorance on electric. I want to do this in the least invasive way and I am hoping that I can use this box to extend my lighting.
By the way, the light switch in my kitchen controls the box, which would be ideal in this setup.
Any thoughts?
Frank
Sent from my iPhone
Reply via web post | Reply to sender | Reply to group | Start a New Topic | Messages in this topic (3) |
Re: [DIY] Electric Question
It depends on the current load of the circuit and what size of new lights you plan to use. Find the breaker controlling the existing light and see what else it turns off. Find this out and let us know.
On 6/24/2013 9:53 PM, Frank Ruggiero wrote:
Hi Electricians.
I am hoping to build 3 light columns in my backyard. I noticed I have a junction box mounted to my foundation which powers a light above my back door.
Is it possible to tap into that box to power the 3 additional light columns.
Does anyone see an issue with powering 4 lights from one standard box?
Excuse my ignorance on electric. I want to do this in the least invasive way and I am hoping that I can use this box to extend my lighting.
By the way, the light switch in my kitchen controls the box, which would be ideal in this setup.
Any thoughts?
Frank
Sent from my iPhone
Reply via web post | Reply to sender | Reply to group | Start a New Topic | Messages in this topic (2) |