Thanks for confirming. I was about 99% sure that 2/0 AUG is what I needed for the power, and 4 AUG for the ground.
Any suggestions for a disconnect? Not finding much. I want one to sit on the inside of the wall from the meter. I do not want a disconnect on the outside. then I will run the 2/0 cables from there to the panel.
From: DoIt_Yourself@yahoogroups.com [mailto:DoIt_Yourself@yahoogroups.com] On Behalf Of wired
Sent: Monday, February 11, 2013 7:48 PM
To: DoIt_Yourself@yahoogroups.com
Subject: Re: Update RE: [DIY] Electrical troubles
Look up NEC (National Electrical Code)table 310.15(B)(6).
Single phase 3 wire service for residential requires 1AWG for 150 amp and 2/0 AWG for 200 amp.
__._,_.___
Reply via web post | Reply to sender | Reply to group | Start a New Topic | Messages in this topic (23) |
Please send decorating questions to Interior Motives List - to subscribe send an email to: Interior_Motives-subscribe@yahoogroups.com
.
__,_._,___
No comments:
Post a Comment