Cartoon Network

12 February 2013

Re: Update RE: [DIY] Electrical troubles

 

I'm inclined to stick with either Square D or Cuttler Hammer.  Trick to remember. Run the conduit and wire first then set the box.  Its a whole lot easier that way.
Dale in the Flatlands.
Michael Baldwin wrote:
 

Thanks for confirming. I was about 99% sure that 2/0 AUG is what I needed for the power, and 4 AUG for the ground.
Any suggestions for a disconnect? Not finding much. I want one to sit on the inside of the wall from the meter. I do not want a disconnect on the outside. then I will run the 2/0 cables from there to the panel.
 
Michael

From: DoIt_Yourself@yahoogroups.com [mailto:DoIt_Yourself@yahoogroups.com] On Behalf Of wired
Sent: Monday, February 11, 2013 7:48 PM
To: DoIt_Yourself@yahoogroups.com
Subject: Re: Update RE: [DIY] Electrical troubles

 


Look up NEC (National Electrical Code)table 310.15(B)(6).
Single phase 3 wire service for residential requires 1AWG for 150 amp and 2/0 AWG for 200 amp.


__._,_.___
Reply via web post Reply to sender Reply to group Start a New Topic Messages in this topic (25)
Recent Activity:
Please send decorating questions to Interior Motives List - to subscribe send an email to: Interior_Motives-subscribe@yahoogroups.com
.

__,_._,___

No comments:

Post a Comment