With a 60 amp breaker in the house, you need #6 minimum. As you stated, you are running PVC conduit. I would use 1" and THHN single conductor wire instead of romex. You can either run 3 wires + a #10 ground wire or just 3- #6"s and put a ground rod @ the shed connected to the neutral bar in the panel. If you run a seperate ground, isolate the grounds from the neutral. Also connect any metal water pipes to the ground as well.