Re: [DIY] Electrical question

 

It is OK to put an additional 120 volt load on 1 hot and a neutral.  But do you have a neutral (not ground) present on the 240 volt pump circuit?



On 5/31/2013 4:56 PM, Ed wrote:
 

Hi all, I have a deep well with a submersible pump that runs on 240V. Could I safely install a 10W light bulb on one the 2 normally open 120V volt legs that go to make up the 240, or do I have to keep the same exact load on both legs. The reason that I want to do this is that I have a remote security camera and when I'm away I could check the light bulb to see if my pump is active when it should be irrigating the landscaping. Thank for any advice, Ed