Cartoon Network

01 June 2013

[DIY] Electrical question

 

Hi all, I have a deep well with a submersible pump that runs on 240V. Could I safely install a 10W light bulb on one the 2 normally open 120V volt legs that go to make up the 240, or do I have to keep the same exact load on both legs. The reason that I want to do this is that I have a remote security camera and when I'm away I could check the light bulb to see if my pump is active when it should be irrigating the landscaping. Thank for any advice, Ed

__._,_.___
Reply via web post Reply to sender Reply to group Start a New Topic Messages in this topic (5)
Recent Activity:
Please send decorating questions to Interior Motives List - to subscribe send an email to: Interior_Motives-subscribe@yahoogroups.com
.

__,_._,___

No comments:

Post a Comment